5.2.2 Wiring Check
(1) Insert the Test Lead into the instrument.(Fig.15)
(2) Connect test lead to object to be tested.(Fig.11,12,13,14)
(3) Make sure that the P-E and P-N wiring Check LEDs are lit and the
wiring in correct LED is not lit. If it is not correct, disconnect the
tester and check the wiring for a possible fault.
5.2.3 Testing
(1) Press the test button. A beep will sound as the test is conducted and
the value of loop impedance will be displayed.
Note: When Test Lead removed during a measurement, "no" is
displayed on LCD and a measurement will be stopped. Please
check Test Lead is rightly connected.
● LOOP range
● PSC range
LOOP Range
PSC Range
2000Ω
200A
The Initial value
#
CAUTION
The RCD of a circuit shall be bypassed when measuring on LOOP 20
Ω range. Do not operate the Test button on RCD while RCD is
bypassed. Be sure to get back the bypassed RCD after test.
Fig.15