MODEL
1A
MULTI-FUNCTION TESTER
INSTRUCTION MANUAL
KYORITSU ELECTRICAL INSTRUMENTS WORKS,LTD.
Zobrazit stránku 0
1 2 3 4 5 6 ... 31 32

Shrnutí obsahu

Strany 1 - MULTI-FUNCTION TESTER

MODEL6011AMULTI-FUNCTION TESTERINSTRUCTION MANUALKYORITSU ELECTRICAL INSTRUMENTS WORKS,LTD.

Strany 2 - CONTENTS

―8―The influencing variations used for calculating the operating error are denoted as follows;Temperature: 0 ℃and 35 ℃Supply voltage : 8V to 13.8V● Op

Strany 3 - 1. SAFE TESTING

―9―LED indication of livecircuit warningLED indication of correctPolarity5.DC power source: 12.0 V, ripple content 1% orless6. Altitude up to 2000mBat

Strany 4

―10―4. CONTINUITY(RESISTANCE)TESTSWARNINGENSURE THAT CIRCUITS TO BE TESTED ARE NOT LIVE.DISCONNECT THE INSTRUMENT FROM THE CIRCUIT UNDER TEST BEFORE O

Strany 5 - 2. FEATURES

―11―turned to the OFF position. The memorized null value can be cancelled bydisconnecting the test leads and pushing the AUTO NULL/Uc SWITCH withthe

Strany 6

―12―5. INSULATION TESTSWARNINGENSURE THAT CIRCUITS TO BE TESTED ARE NOT LIVE.DISCONNECT THE INSTRUMENT FROM THE CIRCUIT UNDER TEST BEFORE OPERATING TH

Strany 7

―13―Fig 45.1.3 Conduction CurrentSince the insulation resistance is not infinite, a small leakage current flowsthrough the insulation between condu

Strany 8 - 3. SPECIFICATION

―14―5.1.5 Total Leakage CurrentThe total leakage current is the sum of the capacitive, conduction and surfaceleakage current described above. Each of

Strany 9 - Operating error

―15―¡ Electronic fluorescent starter switches¡ Passive infra-red detectors (PIRs)¡ Dimmer switches¡ Touch switches¡ Delay timers¡ Power controllers¡ E

Strany 10

―16―Note:Insulation testing must only be undertaken on de-energised circuits.3.If the mains warning lamp lights and/or the buzzer sounds DO NOT PRESS

Strany 11

―17―6.When testing is complete release the test button BEFORE disconnecting thetest leads from the circuit or from the appliance. This will ensure t

Strany 12

1.Safe Testing... 12.Features...

Strany 13

―18―6. LOOP IMPEDANCE TESTSDISCONNECT THE INSTRUMENT FROM THE CIRCUIT UNDER TESTBEFORE OPERATING THE FUNCTION SWITCHTO SELECT THE LOOP TESTING RANGE S

Strany 14 - 5. INSULATION TESTS

―19―6.4 The loop impedance testWARNINGDO NOT PROCEED WITH TESTING UNLESS THE P-E AND P-NLAMPS ARE LIT TO CONFIRM THAT THE WIRING IS CORRECTLYCONNECTE

Strany 15

―20―Fig 96.5 Loop impedance at 3 phase equipmentIn order to test the Loop impedance at 3 phase equipment the optional OMADIEC(Model7133)

Strany 16

―21―Fig 10BLACK NEUTRALRED PHASEGREEN EARTH7. PROSPECTIVE SHORT CIRCUIT CURRENT(PSC)TESTSWARNINGNEVER CONNECT THIS INSTRUMENT ACROSS 2 PHASES.N EVER A

Strany 17

―22―8. RCD TESTSDISCONNECT THE INSTRUMENT FROM THE CIRCUIT UNDER TESTBEFORE OPERATING THE FUNCTION SWITCHTO SELECT THE RCD TEST RANGE SELECT“RCD”8.1 P

Strany 18

―23―8.2 What does the RCD test really do?The RCD is designed to trip out when the difference between the phase currentand the neutral current (this is

Strany 19

―24―4.Connect the instrument to the RCD to be tested either via a suitable socketoutlet(see fig 9)or using the OMA DIEC(Model7133) test lead set(seefi

Strany 20 - 6. LOOP IMPEDANCE TESTS

―25―display.6.Press the phase selector switch to indicate 180™in the display and repeatthe test.7.MAKE SURE TO KEEP CLEAR OF EARTHED METAL DUR

Strany 21

―26―9. The external earth terminal.The external earth terminal at the ranges of Loop, PSC and RCD, the buzzerwarns that the mains earth is switched to

Strany 22 - PHASES AT THE SAME TIME

―27―10. GENERAL11. BATTERY REPLACEMENTWhen the display shows the low battery indication, ( ), disconnect the testleads from the instrument. Remove

Strany 23 - GREEN EARTH

―1―1. SAFE TESTINGElectricity is dangerous and can cause injury and death. Always treat it with thegreatest of respect and care. If you are not quite

Strany 24 - 8. RCD TESTS

―28―If this tester should fail to operate correctly, return it to your distributor statingthe exact nature of the fault. Before returning the instr

Strany 25

―29―14. CASE AND STRAP ASSEMBLYCorrect assembly is shown in Fig 12. By hanging the instrument round the neck,both hands will be left free for testing.

Strany 26

92-1530D 05-02DISTRIBUTORKyoritsu reserves the rights to change specifications or designs described inthis manual without notice and without obligatio

Strany 27

―2―barriers on the test leads.11.During testing it is possible that there may be a momentary degradation ofthe reading due to the presence of excessiv

Strany 28

―3―2. FEATURESMΩ AUTO NULL/Uc SWITCH Test Lead with IEC ConnectorLCD DISPLAYTest Lead for Continuity and Insulation TestingFig.1

Strany 29 - 12. FUSE REPLACEMENT

―4―Model 6011A Multi-Function tester performs six functions in one instrument.1.Continuity tester2.Insulation resistance tester3.Loop impedance tester

Strany 30 - 13. SERVICING

―5―Over temperature protection Detects overheating of the internal resistor(used for loop and PSC tests) and of thecurrent control MOS FET (used for R

Strany 31 - 14. CASE AND STRAP ASSEMBLY

―6―3. SPECIFICATIONMeasurement SpecificationFunctionContinuityOpen CircuitVoltage (DC)Short CircuitCurrentRangeAccuracyGreater than 6 VGreater than200

Strany 32 - DISTRIBUTOR

―7―FunctionRatedVoltageMeasuring Range AccuracyVoltage Measurement-100-250V100-250V3% rdgTo prevent wrong connection of test leads and to maintain saf